PVC Insulation Armoured Power Cable MV 6/10KV 8.7/15KV 12/20KV 18/30KV
Contact Person : Andrea
Phone Number : 0086-371-60547601
WhatsApp : +8613598873045
Detail Information |
|||
Conductor: | Class 2 Stranded Copper Conductor | Insulation: | XLPE |
---|---|---|---|
Bedding: | PVC | Armour: | SWA (Steel Wire Armour) |
Sheath: | PVC | Voltage Rating: | 600/1000V |
High Light: | armoured electrical cable,electrical power cable |
Product Description
BS 5467 Copper Conductor Multi Core SWA PVC rated voltage 0.6/1kV Cable
APPLICATION
Multi-core PVC cable with steel wire armour (SWA). Power and auxiliary control cables for use in power networks, underground, outdoor and indoor applications and for use in cable ducting.
CONSTRUCTION
Conductor
Class 2 stranded copper conductor according to
BS EN 60228 (previously BS 6360)
Insulation
XLPE (Cross-Linked Polyethylene)
Bedding
PVC (Polyvinyl Chloride)
Armour
SWA (Steel Wire Armour)
Sheath
PVC (Polyvinyl Chloride)
CHARACTERISTICS
Voltage Rating (Uo/U)
600/1000V
Temperature Rating
Fixed: -25°C to +90°C
Minimum Bending Radius
1.5mm2 to 16mm2 - Fixed: 6 x overall diameter
25mm2 and above - Fixed: 8 x overall diameter
Core Identifcation
2 core: Brown Blue
3 core: Brown Black Grey
4 core: Brown Blue Black Grey
5 core: Green/Yellow Brown Blue Black Grey
Alternative Core Identifcation:
White cores with Black numbers
Sheath Colour
Black
Data Sheet
A
NO. OF CORES |
NOMINAL CROSS SECTIONAL AREA mm² |
NOMINAL THICKNESS OF INSULATION mm |
NOMINAL DIAMETER mm |
NOMINAL WEIGHT kg/km |
|
Under Armour |
Overall | ||||
2 2 2 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 4 4 4 4 4 4 4 4 4 4 4 |
1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 1.5 2.5 4 6 10 16 25 35 50 70 95 |
0.6 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1 1.1 1.1 1.2 1.4 0.6 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1 1.1 1.1 1.2 1.4 1.6 1.7 1.8 2 0.6 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1 1.1 1.1 |
7.3 8.5 9.4 10.5 12.3 14.3 14.7 16.8 19 22 25.1 27.9 30.9 7.8 9.2 10 11.2 13.1 15.3 18.9 21.3 21.7 25.2 28.8 32 35.9 40 44.9 49.8 55.8 8.5 9.9 11 12.3 14.5 17 21 23.6 25 29.5 33.3 |
12.1 13.6 14.7 15.9 18 20.4 20.4 23.3 25.8 29 33.1 36.1 39.3 12.6 14.1 15.3 16.6 19.5 21.6 23.6 25.7 28.5 32.2 37 40.4 45.5 49.8 55.1 60.2 66.6 13.3 15 16.4 18.7 21.1 23.4 26.1 28.6 32 37.7 41.7 |
302 346 410 499 648 978 1290 1500 1890 2450 3300 4020 4750 330 390 464 568 866 1152 1800 2230 2490 3290 4440 5470 6930 8350 10400 12600 14600 365 438 532 764 1013 1360 2160 2690 3130 4500 5600 |
B
NOMINAL CROSS SECTIONAL AREA mm² |
MINIMUM NO. OF WIRES IN CONDUCTOR | MAXIMUM RESISTANCE OF CONDUCTOR AT 20ºC | |||||
Circular | Circular Compacted | Shaped | Annealed Copper Conductor | ||||
CU | AL | CU | AL | CU | AL | Plain Wires ohms/km |
|
1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 |
7 7 7 7 7 7 7 7 19 19 19 37 37 37 37 61 61 |
- - - - 7 7 7 7 19 19 19 37 37 37 37 61 61 |
6 6 6 6 6 6 6 6 6 12 15 18 18 30 34 34 53 |
- - - - 6 6 6 6 6 12 15 15 15 30 30 30 53 |
- - - - - - 6 6 6 12 15 18 18 30 34 34 53 |
- - - - - - 6 6 6 12 15 15 15 30 30 30 53 |
12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.047 |
C
NOMINAL CROSS SECTIONAL AREA mm² |
REFERENCE METHOD C (CLIPPED DIRECT) Amps |
REFERENCE METHOD E (IN FREE AIR OR ON A PERFORATED CABLE TRAY, HORIZONTAL OR VERTICAL) Amps |
REFERENCE METHOD D (DIRECT IN GROUND OR IN DUCTING IN GROUND, IN OR AROUND BUILDINGS) Amps |
|||
1 Two Core Cable Single-Phase AC or DC |
1 Three or 1 Four Core Cable Three-Phase AC |
1 Two Core Cable Single-Phase AC or DC |
1 Three or 1 Four Core Cable Three-Phase AC |
1 Two Core Cable Single-Phase AC or DC |
1 Three or 1 Four Core Cable Three-Phase AC |
|
1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 |
27 36 49 62 85 110 146 180 219 279 338 392 451 515 607 698 787 |
23 31 42 53 73 94 124 154 187 238 289 335 386 441 520 599 673 |
29 39 52 66 90 115 152 188 228 291 354 410 472 539 636 732 847 |
25 33 44 56 78 99 131 162 197 251 304 353 406 463 546 628 728 |
25 33 43 53 71 91 116 139 164 203 239 271 306 343 395 446 - |
21 28 36 44 58 75 96 115 135 167 197 223 251 281 324 365 - |
D
NOMINAL CROSS SECTIONAL AREA mm² |
TWO CORE CABLE DC |
TWO CORE CABLE SINGLE-PHASE AC mV/A/m |
THREE OR FOUR CORE CABLE THREE-PHASE AC mV/A/m |
||||
1.5 2.5 4 6 10 16 |
31 19 12 7.9 4.7 2.9 |
31 19 12 7.9 4.7 2.9 |
27 16 10 6.8 4 2.5 |
||||
r | x | z | r | x | z | ||
25 35 50 70 95 120 150 185 240 300 400 |
1.85 1.35 0.98 0.67 0.49 0.39 0.31 0.25 0.195 0.155 0.12 |
1.85 1.35 0.99 0.67 0.50 0.40 0.32 0.26 0.20 0.16 0.13 |
0.160 0.155 0.155 0.150 0.150 0.145 0.145 0.145 0.140 0.140 0.140 |
1.900 1.350 1.000 0.690 0.520 0.420 0.350 0.290 0.240 0.210 0.190 |
1.600 1.150 0.860 0.590 0.430 0.340 0.280 0.220 0.175 0.140 0.115 |
0.140 0.135 0.135 0.130 0.130 0.130 0.125 0.125 0.125 0.120 0.120 |
1.650 1.150 0.870 0.600 0.450 0.370 0.300 0.260 0.210 0.185 0.165 |